12. Storage facilities must be equipped, on the entire outer perimeter, with a drain placed at the same level or below the floor or bottom. The drain must not be connected to the storage facility and its outlet must be linked to a port with a minimum inside diameter of 40 cm accessible for sample-taking.
A permanent marker must indicate the drain outlet’s location.
The drain must be functional at all times and evacuate water by gravity or pumping.