4.2.2. In any low hazard establishment, or medium hazard establishment protected with automatic extinguishers, non-enclosed vertical openings are allowed, provided that:(a) these openings do not connect more than 3 communicating floors;
(b) the lowest level or the one above is at ground level;
(c) the 3 communicating floors are unobstructed so that the beginning of a fire can be easily detected;
(d) the capacity of exits can accommodate the occupant load of the 3 storeys;
(e) each storey considered separately, has at least one half of its required exits leading directly to an area isolated with a partition having a fire resistance of 2 hours;
(f) any other requirement of Division IV is observed.