52. Unless it is permanently enclosed, every hoisting compartment of a shaft shall have a gate at each shaft station. The gate shall:(1) be at least 1.2 m (3.9 ft) in height;
(2) have less than 80 mm (3.1 in) clearance between the floor and its lower edge;
(3) withstand a concentrated horizontal force of at least 1 kN (224.8 lb) applied at any point on the gate;
(4) withstand a concentrated horizontal force of at least 100 kN (22,481 lb) applied at any point on the gate if a travelway can bring a vehicle right to the gate;
(5) remain closed, except when a conveyance is loaded or unloaded at the shaft station.