425. The distribution of electricity in explosives magazines shall comply with the following standards:(1) the maximum voltage of lighting circuits may not exceed 150 V to the ground;
(2) the conductors shall be installed in a rigid conduit with screwed and watertight joints or in an armoured moisture-proof cable;
(3) the lighting fixtures shall be dustproof;
(4) the protective devices and control devices shall be installed in a cabinet placed outside the magazine;
(5) the lighting circuit overload protection shall not exceed 10 A;
(6) the circuits shall be open before the fixtures are opened to change the bulbs;
(7) the metal parts shall be interconnected and permanently grounded.