506. Cable couplers on circuits operating at voltages higher than 300 V shall be:(1) of a type designed for the cables on which they are used;
(2) of a design and dimensions suitable for the worst conditions under which they are used;
(3) equipped with covering, hoods or seals to cover the unprotected ends when they are disconnected;
(4) equipped with cable clamps and gaskets on the joints to prevent any infiltration of water;
(5) designed so that they comply with one of the following requirements designed to prevent accidental disconnection when they are energized:(a) special tools shall be used to separate the sections;
(b) the sections shall be held together by a padlock;
(c) a control circuit shall be included and shall trip the cable circuit breaker to de-energize the phase terminals before separating them.