Q-2, r. 9.01 - Design code of a storm water management system eligible for a declaration of compliance

Full text
148. The average water flow speed, V, during the passage of the flow having a 5-year return period must not exceed the values indicated in Table 4.7 according to the type of vegetation in place, the draining slope and the nature of the soils.
Table 4.7 Average water flow speed
Type of vegetation in the ditchSlope
(%)
Speed
(m/s)
Erosion-resistant soilNon-erosion-resistant soil
Well-rooted grass0-52.441.83
5-102.131.52
> 101.831.22
Short-blade grass0-52.441.52
5-101.831.22
> 101.520.91
Mixture0-51.521.22
5-101.220.91
Grasses0-51.070.76
O.C. 871-2020, s. 148.
In force: 2020-12-31