88. Fuel burning equipment using fuel other than fuel referred to in Divisions III and IV of this Chapter must not emit particles into the atmosphere in excess of the following limits:(1) the limits prescribed by section 64, according to the rated heat capacity of the equipment, in the case of fuel that is exclusively in a liquid or gaseous state at the feed point; or
(2) 100 mg/Rm3 of dry gas for existing equipment and 70 mg/Rm3 of dry gas for new equipment in all other cases, the measured concentration being corrected to 7% of oxygen according to the formula in the first paragraph of section 79.
This section does not apply to the use of fuel consisting of used oil in accordance with the second paragraph of section 26 of the Regulation respecting hazardous materials (chapter Q-2, r. 32).