M-6, r. 1 - Regulation respecting stationary enginemen

Full text
SCHEDULE B
(s. 11)
REMOTE CONTROLS

REMOTE CONTROLS



Measure Instrument
and
Control
Apparatus




Stationary
Engines
Water level indicator Low-water alarm High-water alarm Pressure, steam or
hot water indicators Heavy oil temperature
indicator Fuel atomization
pressure indicator Water intake
pressure indicator Intake pump on/off
indicator Energy source on/off
indicator On/off indicator or differential pressure
indicator for draft fans Flame dectector
operation indicator** Emergency
stop Hot water or thermal liquid
temperature indicator Flow-meter Bearing temperature indicator or
lubricating oil pressure indicator Compressor lift and
suction pressure indicator
Steam boilers X X X X X X X X X X X X
Electric steam boilers X X X X X X X X
Hot-water boilers X X X X X X* X X X X X
Electric hot-water boilers X X X X X X
Coiled tube boilers X X X X X X X X X X X X
Thermal liquid boilers X X X X X X X X X X
Steam generators X X X X X X X
Refrigerating apparatus X X X X

* Applicable to high-temperature and high-pressure hot-water boilers.
** In the case of burners in continuous operation, gas pilot flames for oil burners,
minimum flow controls for gas or oil burners and release devices for gas low-pressure may replace flame detectors.
R.R.Q., 1981, c. M-6, r. 1, Sch. B.