E-1.1, r. 1 - Regulation respecting energy conservation in new buildings

Full text
138. When the temperature of the exhaust air exceeds 30 ºC, the sensible heat content of the exhaust air in kilowatts shall be calculated by using the formula:
Cs = Q c (tc - to)
_______________
1,000 V
Where
Cs = sensible heat content in KW
Q = rated capacity of the building exhaust air system in L/s
c = specific heat of the exhaust air at exhaust air conditions in kJ/(kg • ºC)
v = specific volume of the exhaust air at exhaust air conditions in m3/kg
te = temperature of the exhaust air before passing through any heat recovery apparatus in ºC
to = outdoor design temperature for heating purposes in ºC.
O.C. 89-83, s. 138.