Temperatures for standard rating conditions for water
chillers and heat pumps, °C
Type of water chillers
______________________________________
a) centrifugal Reciprocating Hydronic
compressors without integral system water
b) self-contained condensers source heat
reciprocating pumps
compressors
Water temperature leaving
chiller 6.7 6.7 -
Water temperature entering
chiller 12.2 12.2 -
Water temperature leaving
condenser 35.0 - 35.0
Water temperature entering
condenser 29.4 - 29.4
Air temperature entering indoor 26.7 dry bulb
portion of heat pump - - 19.4 wet bulb
Air temperature surrounding 35.0 dry bulb
air or evaporative cooled 23.9 wet bulb - -
condenser
Refrigerant saturation
temperature at the discharge
of water or evaporative
cooled compressor - 40.6 -
Refrigerant saturation
temperature at the discharge
of air-cooled compressor - 48.9 -
Liquid refrigerant
temperature for
water or evaporative
cooled condenser - 35.0 -
Liquid refrigerant
temperature for
air-cooled condenser - 43.3 -
Air temperature
surrounding heat
pump - - 26.7