E-1.1, r. 1 - Regulation respecting energy conservation in new buildings

Full text
124. The coefficient of performance for the equipment mentioned in section 122 shall be determined on the basis of the rating conditions in the following table and in section 127.
TABLE
(s. 124)


Air temperature, °C
___________________________

Heating or cooling medium Dry bulb Wet bulb Water temperature, °C



Air, entering equipment 26.7 19.4 -


Air, surrounding air-cooled
condenser 35 23.9 -


Water, condenser inlet - - 29.4


Water, condenser outlet - - 35

O.C. 89-83, s. 124.