E-1.1, r. 1 - Regulation respecting energy conservation in new buildings

Full text
109. Any piping used in the heating or cooling of a building, and carrying a fluid with a temperature of less than 13 ºC or more than 50 ºC, must be provided with thermal insulation in accordance with the requirements of the following Table, when the heat loss or heat gain from the piping will increase the energy requirements of the building for lack of insulation.
However, this provision does not apply to piping in heated spaces in a dwelling unit that serves only that unit, or piping that is part of a heating or cooling unit.
TABLE
(s. 109)



Insulation thickness (1) in mm


Fluid temperature Nominal pipe size
range °C _________________________________________________________________

1 in 1 1/4 to 2 in 2 1/2 to 4 in 5 and 6 in 8 in
and less and +



151 - 240 64 64 76 89 89


121 - 150 51 64 64 76 76


96 - 120 38 38 51 51 51


50 - 95 25 25 38 38 38


5 - 13 13 19 25 25 25


below 5 25 38 38 38 38

Note:
1. The above Table is based on insulation with a thermal resistivity in the range of 28 to 32 mºC/W, where the thermal resistivity is determined by using the thermal conductivity measured at an average temperature of 24 ºC in accordance with ASTM-C177-85, Standard Test Method for Steady-State Heat Flux Measurements and Thermal Transmission Properties by Means of the Guarded Hot Plate Apparatus. For insulation with a thermal resistivity of less than 28 mºC/W, the thickness is determined by multiplying the thickness values in the Table by 28/R, where R is the actual thermal resistivity of the insulation. For insulation with a thermal resistivity of more than 32 mºC/W, the thickness is determined by multiplying the thickness values in the Table by 32/R, where R is the actual thermal resistivity of the insulation.
O.C. 89-83, s. 109; O.C. 1721-85, s. 19; O.C. 1211-92, s. 15.