Despite section 227, a motor fuel dispenser installed inside a building before 1 April 2007 must meet the following conditions:(1) the dispensing area must have a continuous mechanical ventilation system electrically connected to the dispenser in such manner that the dispenser may only operate while the ventilation is operating at full capacity; and
(2) the dispensing area must be protected by an automatic dry-chemical fire extinguishing system.